ADL3000-E Series Multi-function Energy Meter

UL Certification Three Phase Energy Meter

ADL3000-E is a smart meter designed for power supply system, industrial and mining
enterprises and utilities to calculate the electricity consumption and manage the electric demand. It
features the high precision, small size and simple installation. It integrates the measurement of all
electrical parameters with the comprehensive electricity metering and management provides
various data on previous 12 months, checks the 31st harmonic content and the total harmonic
content, realizes the remote communication and the remote control with switching input . It is
fitted with RS485 communication port and adapted to MODBUS-RTU. ADL3000-E can be
used in all kinds of control systems, SCADA systems and energy management systems. All meters
meet the related technical requirements of electricity power meter in the IEC62053-21、
IEC62053-22 standards.
ADL3000-E-2.jpg
         

Main Feature 

● Rated Current: 1 (6) A, 10 (80) A, 3*10(100)A External CT

● Rated Voltage: 3×100V, 3×380V, 3×57.7/100V, 3×220/380V

● Active power、Voltage、Current、Power factor、Harmonics

● Communication: RS485 (MODBUS-RTU)

● 12 digits LCD Display

● 35mm DIN Rail Installation

● 2~31st Harmonic Measurement

● CE , UL Certificated

 


Overview

 


Parameter

Project

Performance parameter

Specification

3 phase 3 wires, 3 phase 4 wires

 

 

 

 

 

Measurement

 

Voltage

Reference voltage

3 × 100V, 3×380V, 3×57.7/ 100V, 3×220/380V

Consumption

<10VA(Single phase)

Impedance

>2MΩ

Accuracy class

Error±0.2%

 

Current

Input current

3×1(6)A, 3×10(80)A, 3*10(100)A External CT

Consumption

<1VA Single phase rated current

Accuracy class

Error±0.2%

Power

Active, reactive, apparent power, error ±0.5℅

Frequency

45~65Hz ,Error±0 2%

 

Metering

Energy

Active energy (Accuracy class: 0.5)

Reactive energy (Accuracy class 2)

Clock

≤0.5s/d

Digit signal

Energy pulse output

1 active photocoupler output

Pulse

Width of pulse

80±20ms

Pulse constant

400imp/kWh, 10000imp/kWh(Correspond with the basic current)

Communication

Interface and communication protocol

RS485:Modbus RTU

Range of communication address

Modbus RTU:1~ 247;

Baud rate

1200bps~19200bps

Environment Working temperature

-25℃~+55℃

Relative humidity

≤95℅(No condensation)

 


Wiring

 

① Seal for Anti theft

② Brand

③ Panel

④ Enter-wire

⑤ Auxiliary function

⑥ Pulse output light

⑦ Button

⑧ Outlet wire

 

 

 

 

CT CONNECTION

DIRECT CONNECTION

 

 

 


Network


Package

MINIMUM PACKAGE

 

 

MINIMUM PAKAGE

Package dimensions(1 PC)

170*150*130mm

Pakage Weight(1 PC)

0.5Kg

 

WHOLE BOX PAKAGE

 

Package dimensions(36 PCS)

450*240*250mm

Pakage Weight(36 PCS)

18.5kG

 

PRODUCT HS CODE

 

9028301400

 


FAQ

Q: What’s the difference of current input via direct connect or via CTs?

A: Normally, for 3-phase loads with rated current below 80A AC, we will use model of ADL400 whose current input is via direct connect. Specs of “Rated Current: 10(80)A AC” was aimed for this model of ADL400 (current input via direct connect). 10 means basic current is 10A AC, 80 means rated current input is 80A AC.

And for 3-phase loads with rated current over 80A AC, we will use model of ADL400 whose current input is via CTs (usually paired with -/5A CTs whose secondary current output is with 5A AC rated current output). Specs of “Rated Current: 1(6)A AC” was aimed for this model of ADL400 (current input via CTs). 1 means basic current is 1A AC, 6 means max current input is 6A AC.

 

Q: Do your company also have paired CTs for ADL400?

A: Usually, we will recommend our user to use split-core CTs called AKH-0.66/K K-φ Series or solid-core CTs called AKH-0.66/I Series to the paired with ADL400 (current input via CTs)

 

Q: How can I set the CT or PT ratio of ADL400?

A: Current ratio of ADL400 could be set by using the keypads on ADL400 and following the instruction of ADL400 manual. Also, setting need to be according to the CTs or PTs ratio which were paired with ADL400. For example, if the current input is via 250A/5A CTs, the CT ratio on ADL400 should be set to 250/5=50. And if the voltage input is via direct connect, PT ratio on ADL400 should be set to 1. When the problem hasn’t been solved, please contact us for help.

 

Q: Could ADL400 be used in IoT Energy Monitoring System for factory or building?

A: ADL400 has standard RS485 interface and MODBUS-RTU communication protocol which allow it to be integrate with our IoT Energy Monitor Solution that can enable our users to remotely check all the data collect by energy meters like ADL400 on their mobile phone or PC. For more information, please Contact us or check in IoT Energy Monitoring Solution Introduction.

 

Q: What is Multi-rate/tariff function? How does it work?

A: First,multi-rate/tariff function was designed to be used for billing system. Second, the electricity price of different time duration in a day is different in some country.

Energy meter with this function can measure the kwh data and assign them to several time duration in a day and put a label of spike/peak/flat/valley kwh on them respectively. And if such energy meter was connected to the billing system by using a IoT gateway, it can send the kwh data of different time duration which was with the label of spike/peak/flat/valley kwh to the billing system for calculating the electricity bill of different time duration in a day.

For example, the electricity price of spike kwh is 5 USD/1 kwh, and time duration of from 9:00 am to 11:30 am was labeled as spike kwh.
Then, if energy meter record 3 kwh used in total during 9:00 am to 11:30 am, it will send the data of 3 kwh with the label of spike kwh to the billing system, and the system calculate the electricity cost of 3x5=15USD in total from 9:00 am to 11:30 am.

Other Question? Please contact us and we will get back to you as soon as possible.

 


Product Application


Sıcak Ürün:% s

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.

AMC300L Base Station AC Multi-loop Intelligent Power Collection and Monitoring Device

6 channel 3 phase or 18 channel 1 phase

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

With Different Size of CTs,easy to install D10,D16,D24,D36

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.

AMC300L Base Station AC Multi-loop Intelligent Power Collection and Monitoring Device

6 channel 3 phase or 18 channel 1 phase

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

With Different Size of CTs,easy to install D10,D16,D24,D36

Acrel ADW600 Multi Channels Smart 3 Phase Energy Meter

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

AM6 Prefabricated Substation Protection & Control Device

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

ATU Intelligent Monitoring Terminal for Switchgear

Conduct centralized monitoring and management.