ADW310 wireless energy meter is mainly used to measure the active energy of low-voltage network. It has the advantages of small size, high precision, rich functions,etc., and has many optional communication methods. It can support RS485 communication, Lora, 4G and other wireless communication methods. The current sampling mode of the transformer is convenient for users to install and use in different occasions. It can be flexibly installed in the distribution box to meet the needs of power metering, operation and maintenance supervision or power monitoring for different areas and different loads.
Main Feature
● Rated Current: AC 20(100)A
● Rated Voltage: 220V
● Active power、Voltage、Current、Power factor、Harmonics
● Communication: RS485, WiFi, 4G
● Communication Protocol: MODBUS-RTU, MQTT, MODBUS-TCP
● LCD Display
● 35mm DIN Rail Installation
● 2~31st Harmonic Measurement
Overview
![]() |
![]() |

Function

![]() |
Online&Remote Energy Monitoring ● Paired with Acrel IoT EMS ● PC Access via IoT EMS WEB ● Mobile Phone Access via IoT EMS APP ● 4G Wireless Communication (Global) ● WiFi Wiress Communication (2.4GHz) ● Support MQTT, MODBUS-TCP protocol ● Support standard RS485 (MODBUS-RTU) |
Parameter
|
Project |
Performance parameter |
|
|
Specification |
Single phase |
|
|
Voltage input |
Rated voltage
|
220V
|
|
Reference frequency
|
50Hz
|
|
|
Power consumption
|
Each phase <0.5VA
|
|
|
Current input |
Input current |
AC 20(100)A
|
|
Starting current
|
1‰Ib (Class 0.5S),4‰Ib (Class 1)
|
|
|
Power consumption
|
Each phase <1VA
|
|
|
Auxiliary power supply
|
Power supply
|
AC 85~265V
|
|
Power consumption
|
<2W
|
|
|
Measurement performance
|
Standard
|
GB/T17215.322-2008,GB/T17215.321-2008
|
|
Active power accuracy
|
Class 1
|
|
|
Temperature accuracy
|
±2℃
|
|
|
Pulse
|
Pulse length
|
80±20ms
|
|
Pulse constant
|
1600 imp/kWh
|
|
|
Communication
|
Wireless
|
470MHz wireless transform,open space distance :1km;4G
|
|
Interface
|
RS485 (A、B)
|
|
|
Medium
|
Shielded twisted pair
|
|
|
Protocol
|
MODBUS-RTU、DL/T 645-07
|
|
|
Temperature range
|
Work temperature
|
-25℃~55℃
|
|
Storage temperature
|
-40℃~70℃
|
|
|
Humidity
|
≤95%(no condensation)
|
|
|
Altitude
|
<2000m
|
|
Wiring

Network
Package
|
MINIMUM PACKAGE
|
![]() |
![]() |
![]() |
![]() |
|
MINIMUM PAKAGE |
Package dimensions(1 PC) 170*150*130mm |
Pakage Weight(1 PC) 0.5Kg |
||
|
WHOLE BOX PAKAGE
|
Package dimensions(36 PCS) 450*240*250mm |
Pakage Weight(36 PCS) 18.5kG |
||
|
PRODUCT HS CODE
|
9028301400 | |||
FAQ
Q: How to do when the RS485 network communication fault?
A: Please first confirm whether the RS485 wiring is loose, AB reverse connection and other problems, and then click the key to check the table of general parameters Numbers, such as address, baud rate, check bits, etc., are set correctly.
Q: How to do when the LoRa communication fault?
A: Please use the USB to 485 serial port line to connect with the instrument RS485 interface, and read the parameters in the table through communication. Verify whether the parameters in the table are the same as the wireless configuration of the upper main station (channel and spread spectrum factor). If they are different, please modify the instrument wireless parameters to be consistent with the master station and then test again; If the same, it may be the instrument and the master station. Too far apart or serious field interference, at this time can try to use an external suction cup antenna, or consider the nearby new wireless master and test again.
Product Application

Sıcak Ürün:% s

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.