Sıcak Ürün:% s
Main Feature
● Rated Current: 0~(50-1000)A
● Rated Voltage: ±5V/±4V
● Power Supply: DC±12/±15V
● Measuring aperture: Φ40mm
● Standard&Certificate: CE; IEC; LVD
Overview
![]() |
![]() |
![]() |

Parameter
|
Parameters
|
Index
|
|
Rated Input Current
|
0~(50-1000)A
|
|
Rated Output Voltage
|
±5V/±4V
|
|
Accuracy Class
|
1.0
|
|
Power Voltage
|
DC±15V (allowable fluctuation±20%)
|
|
Zero Offset Voltage
|
±20mV
|
|
Offset Voltage Drift
|
≤±1.0mV/℃
|
|
Linearity
|
≤0.2%FS
|
|
Response Time
|
≤5us
|
|
Bandwidth
|
0~20kHz
|
|
Isolation Voltage
|
3.5kV/50Hz/1min
|
|
Operating Temperature
|
-40℃~85℃
|
|
Storage Temperature
|
-40℃~85℃
|
|
Consumption
|
≤0.5W
|
Wiring
![]() |
| Clamp-on (Split-core) Installation on Measuring DC Cable |
![]() |
| Wiring of Auxiliary Power Supply Input&Transduced Signal Output |
Package
|
MINIMUM PACKAGE
|
![]() |
![]() |
![]() |
![]() |
|
MINIMUM PAKAGE |
Package dimensions(1 PC) 170*150*130mm |
Pakage Weight(1 PC) 0.5Kg |
||
|
WHOLE BOX PAKAGE
|
Package dimensions(36 PCS) 450*240*250mm |
Pakage Weight(36 PCS) 18.5kG |
||
|
PRODUCT HS CODE
|
9028301400 | |||
FAQ
Q: What should I do if I have no display when I power on the meter?
A: Check whether the power supply voltage is within the operating voltage range.
Q: What to do if the meter voltage,current,electric energy and other readings are not correct?
A: Check whether the voltage to current ratio is set correctly, whether the connection mode is set as actual, and whether the voltage transformer and current transformer are in good condition.
Q: What if the meter power or power factor is incorrect?
A: Check whether the connection mode, voltage and current phase sequence are correct, and cable connections are correct.
Q: What to do if the instrument communication is abnormal?
A: Please check whether the address, baud rate and parity bit in the communication. Settings are consistent with the host computer, whether the RS485 converter is normal, and whether the wiring is correct. If the check is correct, the resistance above 120 ohm can be connected in parallel at the communication end.
Product Application

Sıcak Ürün:% s

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.