AMC series meters adopt AC sampling technology, which can measure the current, voltage, power, power factor and electric energy parameters in the power grid separately. It can set the magnification through the panel membrane switch. The meters have RS485 communication interface, adopt Modbus protocol; also can convert the power signal into a standard DC analog signal.
Main Feature
● Rated Current: AC 1A, 5A
● Rated Voltage: AC 3×57.7V/100V (100V), 3×220V/380V (400V)
● Active power、Voltage、Current、Power factor、Harmonics
● Communication: RS485 (MODBUS-RTU)
● LCD Display
● 2~31st Harmonic Measurement
● IEC Certificated
Overview


Parameter
|
Technical parameters
|
Value
|
|
|
Input
|
Connection |
3 phase 4 wire, 3 phase 3 wire |
|
Frequency |
45~65Hz |
|
|
Voltage |
Rating: AC 100V, 400V |
|
|
Overload: 1.2 times rated value(continuous); 2 times rated value(1 second) |
||
|
Power consumption: < 0.5VA |
||
|
Current |
Rating: AC 1A, 5A |
|
|
Overload: 1.2 times rated value(continuous); 10 times rated value (1 second) |
||
|
Power consumption:< 0.5VA |
||
|
Output |
Energy
|
Pulse width: 80±20ms |
|
Pulse constant: 10000, 40000, 160000 imp/kWh |
||
|
Communication |
RS485 (Modbus-RTU) |
|
|
Function
|
Switching input |
2 channels or 4 channels passive contact input mode |
|
Switching output |
Output mode:2 channel relay NO contact output |
|
|
Analog output |
Contact capacity: 3A/30V DC, 3A/250V AC 0~5V,0~20mA,4~20mA programmable |
|
|
Accuracy |
Frequency:0.05Hz,current,voltage:class 0.2, reactive power:class 1.0,reactive energy:class 1.0,other:class 0.5,2~31st harmonic :±1% |
|
|
Auxiliary power supply |
AC/DC 85~265V |
|
|
Power consumption |
≤10VA |
|
|
Insulation resistance |
≥100MΩ |
|
|
Environment
|
Temperature |
Operating: -10°C~+55°C Storage: -25°C ~+75°C |
|
Humidity |
≤93%(no condensation) |
|
|
Altitude |
≤2500m |
|
Wiring
|
|
Network

Package
|
MINIMUM PACKAGE
|
![]() |
![]() |
![]() |
![]() |
|
MINIMUM PAKAGE |
Package dimensions(1 PC) 170*150*130mm |
Pakage Weight(1 PC) 0.5Kg |
||
|
WHOLE BOX PAKAGE
|
Package dimensions(36 PCS) 450*240*250mm |
Pakage Weight(36 PCS) 18.5kG |
||
|
PRODUCT HS CODE
|
9028301400 | |||
FAQ
Q: No display on power?
A: Check whether the supply voltage is within the operating voltage range.
Q: Incorrect reading of voltage,current,electricty,etc?
A: Checking that the voltage/current ratio setting are correct;
Checking whether the wiring mode setting is consistent with the actual situation;
Checking whether the voltage transformer and current transformer are in good condition.
Q: Abnormal communication?
A: Check whether the adress,baud rate,check bits in the communication;
Setting are consistent with the host computer;
Check whether the RS485 converter is normal;
Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.
Product Application

Sıcak Ürün:% s

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.

6 channel 3 phase or 18 channel 1 phase

With Different Size of CTs,easy to install D10,D16,D24,D36

Optional 4DI2DO,12 channels temp measure,4 channels Residual current monitoring

2 × 4–20 mA DC measurement channels and 3 temperature measurement channels

Conduct centralized monitoring and management.
Sorgu